Module libmodbus

lua bindings to libmodbus.

Generally, this provides a very thin layer over libmodbus. Instead of passing the context around to all your modbus_xxx functions, you simply call them as member functions on the context returned by the new() functions.

Info:

  • License: Permission is hereby granted, free of charge, to any person obtaining a copy of this software and associated documentation files (the "Software"), to deal in the Software without restriction, including without limitation the rights to use, copy, modify, merge, publish, distribute, sublicense, and/or sell copies of the Software, and to permit persons to whom the Software is furnished to do so, subject to the following conditions:

    The above copyright notice and this permission notice shall be included in all copies or substantial portions of the Software.

    THE SOFTWARE IS PROVIDED "AS IS", WITHOUT WARRANTY OF ANY KIND, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE WARRANTIES OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE AND NONINFRINGEMENT. IN NO EVENT SHALL THE AUTHORS OR COPYRIGHT HOLDERS BE LIABLE FOR ANY CLAIM, DAMAGES OR OTHER LIABILITY, WHETHER IN AN ACTION OF CONTRACT, TORT OR OTHERWISE, ARISING FROM, OUT OF OR IN CONNECTION WITH THE SOFTWARE OR THE USE OR OTHER DEALINGS IN THE SOFTWARE.

  • Author: Karl Palsson 2016-2020

Functions

version ()
Returns the runtime linked version of libmodbus as a string. The compile time version is available as a constant VERSION.

Returns:

    eg "3.0.6"

See also:

rkt_new_rtu (device, baud, parity, databits, stopbits)
Создать Modbus/RTU контекст - глобальная функция

Parameters:

  • device (required) - "internal" - для встроенного в контроллер RS-485
  • baud rate, defaults to 19200
  • parity defaults to EVEN
  • databits defaults to 8
  • stopbits defaults to 1

Returns:

    a modbus context ready for use
new_rtu (device, baud, parity, databits, stopbits)
Не использовать, а использовать глобальную функцию rkt_new_rtu

Parameters:

  • device (required)
  • baud rate, defaults to 19200
  • parity defaults to EVEN
  • databits defaults to 8
  • stopbits defaults to 1

Returns:

    a modbus context ready for use
new_tcp_pi (host, service)
Create a Modbus/TCP context

Parameters:

  • host eg "192.168.1.100" or "modbus.example.org"
  • service eg "502" or "mbap"

Returns:

    a modbus context ready for use
set_s32 (num)
Write a 32bit (u)int to 2x16bit registers

Parameters:

  • num 32bit number

Returns:

  1. reg1 upper 16bits
  2. reg2 lower 16bits
set_f32le (num)
Write a bit float to 2x16bit registers

Parameters:

  • num floating point number

Returns:

  1. reg1 upper 16bits of a 32bit float
  2. reg2 lower 16bits of a 32bit float
set_f32 (num)
Write a bit float to 2x16bit registers

Parameters:

  • num floating point number

Returns:

  1. reg1 upper 16bits of a 32bit float
  2. reg2 lower 16bits of a 32bit float
get_s16 (1)
16bit register as number to signed 16bit

Parameters:

  • 1 16bit register

Returns:

    signed 16bit number
get_s32 (1, 2)
2x16bit registers as number to signed 32 bit

Parameters:

  • 1 16bit register
  • 2 16bit register

Returns:

    32bit number
get_s32le (1, 2)
2x16bit registers as number to signed 32 bit (reverse order)

Parameters:

  • 1 16bit register
  • 2 16bit register

Returns:

    32bit number
get_u32 (1, 2)
2x16bit registers as number to unsigned 32 bit

Parameters:

  • 1 16bit register
  • 2 16bit register

Returns:

    32bit number
get_u32le (1, 2)
2x16bit registers as number to unsigned 32 bit (reversed order)

Parameters:

  • 1 16bit register
  • 2 16bit register

Returns:

    32bit number
get_f32 (1, 2)
2x16bit registers as number to 32 bit float

Parameters:

  • 1 16bit register
  • 2 16bit register

Returns:

    32bit float
get_f32le (1, 2)
2x16bit registers as number to 32 bit float (Reversed order)

Parameters:

  • 1 16bit register
  • 2 16bit register

Returns:

    32bit float
get_s64 (1, 2, 3, 4)
4x16bit registers as number to signed 64 bit

Parameters:

  • 1 16bit register
  • 2 16bit register
  • 3 16bit register
  • 4 16bit register

Returns:

    64bit number
get_u64 (1, 2, 3, 4)
4x16bit registers as number to unsigned 64 bit

Parameters:

  • 1 16bit register
  • 2 16bit register
  • 3 16bit register
  • 4 16bit register

Returns:

    64bit number

Context Methods

These functions are members of a modbus context, from either new_rtu() or new_tcp_pi()
ctx:connect ()
Connect, see modbus_connect()
ctx:close ()
Close, see modbus_close()
ctx:set_debug (enable)
Set debug

Parameters:

  • enable optional bool, defaults to true
ctx:set_error_recovery (a, b)
Set error recovery, see modbus_set_error_recovery. The arguments will be or'd together.

Parameters:

ctx:set_byte_timeout (seconds, microseconds)
See also modbus_set_byte_timeout

Parameters:

  • seconds (required)
  • microseconds (optional, defaults to 0)
ctx:get_byte_timeout ()

Returns:

  1. seconds
  2. microseconds
ctx:set_response_timeout (seconds, microseconds)

Parameters:

  • seconds (required)
  • microseconds (optional, defaults to 0)
ctx:get_response_timeout ()

Returns:

  1. seconds
  2. microseconds
ctx:get_socket ()

Returns:

    the socket number
ctx:set_socket (sock)

Parameters:

  • sock integer socket number to set
ctx:rtu_get_serial_mode ()

Returns:

    rtu_constants the serial mode, either RTU_RS232 or RTU_RS485
ctx:rtu_set_serial_mode (mode)
Sets the mode of a serial port. Remember, this is only required if your kernel is handling rs485 natively. If you are using a USB adapter, you do NOT need this.

Parameters:

  • mode The selected serial mode from rtu_constants, either RTU_RS232 or RTU_RS485.
ctx:set_slave (unitid)

Parameters:

  • unitid the unit address / slave id to use
ctx:read_input_bits (address, count)

Parameters:

  • address
  • count

Returns:

    an array of results
ctx:read_bits (address, count)

Parameters:

  • address
  • count

Returns:

    an array of results
ctx:read_input_registers (address, count)

Parameters:

  • address
  • count

Returns:

    an array of results
ctx:read_registers (address, count)

Parameters:

  • address
  • count

Returns:

    an array of results
ctx:report_slave_id ()

Returns:

    a luastring with the raw result (lua strings can contain nulls)
ctx:write_bit (address, value)

Parameters:

  • address
  • value either a number or a boolean
ctx:write_register (address, value)

Parameters:

  • address
  • value
ctx:write_bits (address, value)

Parameters:

  • address
  • value as a lua array table
ctx:write_registers (address, value)

Parameters:

  • address
  • value as a lua array table, or a sequence of values.

Usage:

    either
     ctx:write_registers(0x2000, {1,2,3})
     ctx:write_registers(0x2000, 1, 2, 3)

Constants provided for use

Constants used in various functions, either as arguments or returns
rtu_constants
RTU Mode Constants

Fields:

  • RTU_RS232
  • RTU_RS485

See also:

error_recovery_constants
Error Recovery Constants

Fields:

  • ERROR_RECOVERY_NONE
  • ERROR_RECOVERY_LINK
  • ERROR_RECOVERY_PROTOCOL

See also:

exception_codes
Exception codes These are all MODBUS_xxxx upstream in libmodbus.

Fields:

  • EXCEPTION_ILLEGAL_FUNCTION
  • EXCEPTION_ILLEGAL_DATA_ADDRESS
  • EXCEPTION_ILLEGAL_DATA_VALUE
  • EXCEPTION_SLAVE_OR_SERVER_FAILURE
  • EXCEPTION_ACKNOWLEDGE
  • EXCEPTION_SLAVE_OR_SERVER_BUSY
  • EXCEPTION_NEGATIVE_ACKNOWLEDGE
  • EXCEPTION_MEMORY_PARITY
  • EXCEPTION_NOT_DEFINED
  • EXCEPTION_GATEWAY_PATH
other_constants
Other constants

Fields:

generated by LDoc 1.5.0 Last updated 2025-12-11 12:14:42